Description
The SB Series stationary lead-acid batteries are available in two types: vented (flooded) lead-acid batteries and valve-regulated sealed (VRLA) lead-acid batteries.
Typical Applications
- Power stations and power plants
- Railways and signaling equipment
- Substations
- Solar energy
- IT and telecommunications
- Power supply and industrial use
- Safety lighting and emergency power
- Engine starting and switching power supplies
- Marine power supply
- UPS (uninterruptible power supply)
Features and Benefits
- Very low water consumption
- Wide capacity range
- Long service life
- High cycle life
- No acid mist, no corrosion of other equipment
- Safe and reliable
- Simple maintenance and intuitive operation
- Very low internal resistance
- Low self-discharge
- Wide range of applications
Technical Specifications
| Standard | IEC 60896-21/22 |
| Capacity range (Ah) | 50-400 / 35-400 |
| Container material | White PP with talc, meeting UL 94 V-0 |
| Grid alloy (positive and negative) | Low-calcium lead alloy (calcium content <1%) |
| Plates (positive and negative) | Grid plates |
| Electrolyte | Gel, absorbed in glass fiber separators |
| Connector design | Embedded screw type, insulated |
| Design life (years) | 12 / 10-12 |
| Float charge voltage | 2.25 V/cell |
| Equalizing charge voltage | 2.40 V/cell |
| Float current per 100 Ah at 20 °C (float voltage 2.03-2.25 V/cell) | 10-40 mA |
| Horizontal installation | Yes |
| Self-discharge per month (float voltage 2.03-2.25 V/cell, 20 °C) | 2-3% |
| Operating temperature range | -20 to +40 °C |
| Refresh charge interval (20 °C) | 6 months |
SB VRLA Battery Models and Specifications
| Model | C10 (Ah) | C3 (Ah) | C1 (Ah) | Weight (kg) | L (mm) | W (mm) | H (mm) |
|---|---|---|---|---|---|---|---|
| SB 12V 50 | 52.7 | 51.5 | 41.8 | 26.0 | 229 | 177 | 230 |
| SB 12V 60 | 63.2 | 56.5 | 46.1 | 26.5 | 229 | 177 | 230 |
| SB 12V 80 | 80.4 | 78.5 | 63.7 | 37.5 | 344 | 177 | 230 |
| SB 12V 100 | 94.8 | 85.0 | 69.2 | 38.0 | 344 | 177 | 230 |
| SB 12V 110 | 111.1 | 108.0 | 88.1 | 52.0 | 498 | 177 | 230 |
| SB 12V 130 | 128.9 | 115.5 | 94.1 | 52.5 | 498 | 177 | 230 |
| SB 12V 140 | 142.2 | 127.5 | 104.0 | 54.5 | 498 | 177 | 230 |
| SB 6V 170 | 170.0 | 143.1 | 110.0 | 32.0 | 242 | 170 | 275 |
| SB 6V 220 | 220.0 | 185.2 | 142.4 | 41.0 | 308 | 170 | 275 |
| SB 2V 400 | 400.0 | 374.5 | 296.5 | 25.0 | 178 | 154 | 314 |
Capacities (C10, C3, C1) are given to an end voltage of 1.80 V per cell.</p >